450
KNX Dimming
Specifications
Order No.
P. unit
PS
Specifications
Order No.
P. unit
PS
Gira electrical installation systems
Price system (PS) ≠ 1, 14: reduced discount
KNX system
devices, actuators,
sensors
4 x 225 W/VA
DRA
2015002015 00
1
66
C Optional accessories
Power boosters
S3000 uni.LED pow.booster DRA 2383 00
D
192
Features
- Dim actuator with integrated bus coupler.
- Switching and dimming of light bulbs, HV halogen lamps,
dimmable HV-LED lamps, dimmable compact fluorescent lamps,
dimmable inductive transformers with LV halogen or NV-LED
lamps, dimmable electronic transformers with LV halogen or
NV-LED lamps.
- Automatic or manual selection of dimming principle according to
load.
- Idle-state, short-circuit, and excess temperature-proof
- Manual actuation of the outputs independent of the bus.
- Temporary status display can be activated, link via
communication object possible across several actuators.
- Power extension using power boosters.
- To simplify configuration, all existing dimming channels can be
assigned to the same parameters in the ETS and hence identically
parametrised.
- Actively transmitting feedback or status messages can be
delayed globally after a bus voltage recovery or ETS
programming operation.
Dimming outputs
- Independent switching and dimming of the dimming outputs.
- The load type can be specified and the dimming principle
defined: Universal (with automatic calibration procedure),
electronic transformer (capacitive/trailing edge), conventional
transformer (inductive/leading edge), LED (leading edge) or LED
(trailing edge).
- Dimming characteristic curve per channel configurable in time
and value range for adaptation to the respective connected load.
- Dimmable range can be set: Switch-on brightness, basic
brightness and upper dimming limit.
- Performance on receipt of an absolute brightness value can be
set (dimming, brightening, fading).
- Performance during relative dimming up in switched-off state
can be set ( switch channel on, no reaction).
- Switching feedback: Active (transmitting to the bus cyclically or
when there is a change) or passive (object can be read out)
feedback function.
- Blocking function can be parametrised for each channel.
- Time functions (switch-on delay, switch-off delay).
- Staircase light function with advance warning function via
time-controlled reduction of lighting or activation of permanent
lighting.
- Can be integrated in the light scenes: Up to 16 internal scenes
can be parametrised per output.
- Delay time for scene retrieval can be configured.
- Dimming performance can be set when a new scene is called up
(brightening, dimming, fading).
- Visual feedback when saving a scene.
- Brightness value feedback: Active (transmitting to the bus
cyclically or when there is a change) or passive (object can be
read out) feedback function.
- For active feedback objects, the type of update can be set (when
the input object is changed or when the feedback value is
changed). This allows visualizations to be adapted individually.
Technical data
KNX medium:
TP256
Rated voltage:
AC 110 to 230 V, 50/60 Hz
Max. connected load (AC 230 V) per channel
- Light bulbs:
20 to 225 W
- HV halogen lamps:
20 to 225 W
- Wound transformer:
20 to 210 VA
- Tronic transformer:
20 to 225 W
- Wound transformer with
NV-LED:
20 to 100 VA
- electronic transformer with
NV-LED:
typically 20 to 200 W
- HV LED lamps:
typically 1 to 200 W
- Compact fluorescent lamp:
typically 20 to 150 W
Connections
- KNX:
Connection and junction terminal
- Load:
Screw terminals
- Connections:
max. 4 mm²
Dimensions
- Modular widths (MW):
4
Notes
- VDE approval in accordance with EN 60669-1, EN 60669-2-1.
- The maximum connected load depends on the operating mode
selected (leading edge or trailing edge). You will find more
detailed information in the operating instructions.
- Power extension using Gira power boosters.
- Installation on DIN top-hat rail.
- KNX Data Secure compatible.
- Fast application download (long frame support).
- Firmware can be updated using the Gira ETS Service App
(additional software).
Scope of supply
- KNX connection and junction terminal included in the scope of
supply.
4 x 225 W/VA
DRA
2025002025 00
1
26
C Optional accessories
Power boosters
S3000 uni.LED pow.booster DRA 2383 00
D
192
Features
- Dim actuator with integrated bus coupler.
- Switching and dimming of light bulbs, HV halogen lamps,
dimmable HV-LED lamps, dimmable compact fluorescent lamps,
dimmable inductive transformers with LV halogen or NV-LED
lamps, dimmable electronic transformers with LV halogen or
NV-LED lamps.
- Automatic or manual selection of dimming principle according to
load.
- Idle-state, short-circuit, and excess temperature-proof
- Manual actuation of the outputs independent of the bus.
- Temporary status display can be activated, link via
communication object possible across several actuators.
- Parallel connection of several outputs for dimming higher lamp
loads or power extension via power boosters.
- To simplify configuration, all existing dimming channels can be
assigned to the same parameters in the ETS and hence identically
parametrised.
- Up to 6 central functions for common control of all dimming
channels with switching, dimming and value objects.
- Up to 8 independent logic functions for implementing simple or
complex logical operations.
- Actively transmitting feedback or status messages can be
delayed globally after a bus voltage recovery or ETS
programming operation.
Dimming outputs
- Independent switching and dimming of the dimming outputs.
KNX dimming actuator, 4-gang Standard