449
Dimming KNX
Specifications
Order No.
P. unit
PS
Specifications
Order No.
P. unit
PS
Gira electrical installation systems
Price system (PS) ≠ 1, 14: reduced discount
KNX system
devices, actuators,
sensors
2 x 300 W/VA
DRA plus
2172002172 00
1
66
C Optional accessories
System 3000 universal LED power booster DRA
D
192
Features
- Dim actuator with integrated bus coupler.
- Switching and dimming of light bulbs, HV halogen lamps,
dimmable HV-LED lamps, dimmable compact fluorescent lamps,
dimmable inductive transformers with LV halogen or NV-LED
lamps, dimmable electronic transformers with LV halogen or
NV-LED lamps.
- Automatic or manual selection of dimming principle according to
load.
- Idle-state, short-circuit, and excess temperature-proof
- Manual actuation of the outputs independent of the bus (building
site operation also possible).
- Building site operation: Outputs can be operated manually
without bus voltage with operating voltage only.
Functions
- Independent control of the dimming channels.
- Central switching function for control of all dimming channels.
- Delay for actively transmitted feedback messages following bus
voltage recovery.
- Load type and dimming method can be configured: Universal
(with automatic calibration procedure), electronic transformer/LV
LED (capacitive/phase cut), conventional transformer/LV LED
(inductive/phase cut), HV LED (phase cut) or HV LED (phase cut).
- Feedback for "switching" and "brightness value".
- Dimmable brightness range can be set.
- Dimming behaviour and dimming characteristics can be
parameterised.
- Switch-on behaviour for a relative dimming command can be
parameterised.
- Bulb-saving switch-on and switch-off
- Automatic setting and scaling of the dimmable brightness range
when using universal power boosters.
- The performance of a dimming channel in the "OFF" state during
reception of a relative dimming command can be parameterised
(switching and dimming or no response).
- Alarm telegrams for short circuit, overload, and load failure.
- Feedback of connected load type.
- Block function or forced setting function can be parameterised
for each output.
- Time functions (switch-on/off delay, staircase light function).
- Staircase light function with advance warning function via
time-controlled reduction of lighting or activation of permanent
lighting.
- Linking function and up to eight scenes per dimming channel
possible.
- Elapsed operating time meter for recording switch-on time.
- Reactions after bus voltage failure and recovery can be set.
Technical data
KNX medium:
TP256
Rated voltage:
AC 110 to 230 V, 50/60 Hz
Max. connected load (AC 230 V) per channel
- Light bulbs:
20 to 300 W
- HV halogen lamps:
20 to 300 W
- Wound transformer:
20 to 300 VA
- Tronic transformer:
20 to 300 W
- Wound transformer with
NV-LED:
20 to 100 VA
- electronic transformer with
NV-LED:
typically 20 to 100 W
- HV LED lamps:
typ. 3 to 60 W
- Compact fluorescent lamp:
typ. 3 to 60 W
Connected load (AC 110 V) per channel
- Light bulbs:
20 to 150 W
- HV halogen lamps:
20 to 150 W
- Wound transformer:
20 to 150 VA
- Tronic transformer:
20 to 150 W
- Wound transformer with
NV-LED:
20 to 50 VA
- electronic transformer with
NV-LED:
typically 20 to 50 W
- HV LED lamps:
typ. 3 to 30 W
- Compact fluorescent lamp:
typ. 3 to 30 W
Connections
- KNX:
Connection and junction terminal
- Load:
Screw terminals
- Connections:
max. 4 mm²
Dimensions
- Modular widths (MW):
4
Notes
- Power extension using Gira power boosters.
- Installation on DIN top-hat rail.
- VDE approval in accordance with EN 60669-1, EN 60669-2-1.
Scope of supply
- KNX connection and junction terminal included in the scope of
supply.
KNX dimming actuator, 2-gang