432
KNX Flush-mounted actuators
Specifications
Order No.
P. unit
PS
Specifications
Order No.
P. unit
PS
Gira electrical installation systems
Price system (PS) ≠ 1, 14: reduced discount
KNX system
devices, actuators,
sensors
Features
Inputs
- Depending on the ETS parameterisation in the application for
switches, buttons or contacts, inputs 1 and 2 either act internally
on the relay output or separately on the KNX. Input 3 always acts
on the KNX.
- Functions for the inputs when acting on the KNX (switching,
dimming, blind, value transmitter, scene auxiliary unit, 2-channel
operation, controller auxiliary unit, no function).
- Switching: Command for closing and opening of the contact
adjustable (no reaction, ON, OFF, TOGGLE).
- Dimming: Dimming of brightness and/or colour temperature.
Command for closing the contact, time between switching and
dimming, dimming in different steps, telegram repetition in case
of long signal at the input, and sending of a stop telegram at the
end of the dimming process all configurable.
- Blinds: Command for closing the contact and the operating
concept can be parameterised. Times for short and long signal at
input and slat adjustment are adjustable.
- Value transmitter: Functionality as 1-byte, 2-byte, 3-byte or
6-byte value transmitter including colour temperature and colour
value transmitter possible. Individually configurable values. Value
adjustment is optionally possible with a long signal at the input
(not with the 6-byte value transmitter).
- Scene auxiliary unit: Mode of operation (with or without memory
function) and the scene number are adjustable.
- 2-channel operation: When the contact at the input closes, up to
two telegrams can be sent out on the KNX. Operating concept
adjustable (only channel 1 or channel 2/both channels). The mode
of operation of the channels (1-bit, 1-byte, 2-byte, 3-byte, 6-byte)
can be configured separately.
- Controller auxiliary unit: Mode of operation (operating mode
switching, forced operating mode switching, presence function
and target value adjustment) configurable.
- Disabling of all or individual inputs via a 1-bit object possible.
Polarity of the blocking object, behaviour at the beginning and
end of blocking, and behaviour during an active blocking can be
adjusted.
Logic functions
- The device has 8 internal logic functions.
- Logic gate (AND, OR, exclusive AND, exclusive OR, each with up
to 4 inputs).
- 1-bit to 1-byte converter with input filter, blocking object and
specification of output values.
- Blocking element with filter and time functions and blocking
object.
- Comparator for values with 9 different input data formats and
many comparison operations.
- Limit value switch with hysteresis with upper and lower threshold
values for 9 different input data formats. Including specification
of the 1-bit output values.
- The logic functions have their own KNX communication objects
and can process telegrams from the actuator or other bus
devices.
Technical data
KNX medium:
TP256
Connections
- KNX:
Connection terminals to control
line
- Inputs:
Connection terminals to control
line
- Load:
Screw terminals
- Connections:
Max. 4 mm²
Inputs
- Number:
3
Input type:
Zero-voltage
Polling voltage
- Auxiliary inputs:
approx. 5 V
Total length
- Auxiliary input cable:
max. 10 m
Ambient temperature:
-5 °C to +45 °C
Dimensions in mm
- W x H x D:
48
50
28
Notes
- KNX Data Secure compatible.
- Fast application download (long frame support).
Scope of supply
- KNX connection and junction terminal included in the scope of
supply.
Flush-mounted
5061005061 00
1/5
06
C Optional accessories
remote sens. 1493 00
D
370
leakage sensor 5068 00
D
461
condensation sens. 5069 00
D
461
junction box 0070 30
D
134
install.adapter mini hous. 5429 00
D
434
Features
- Switching electrical consumers via a relay contact.
- Device has three inputs with a common reference potential.
- Reading in switching states of installation switches or push
buttons and other zero-voltage contacts at inputs 1 to 3.
- Signal analysis of dew and leakage sensors (see accessories) at
inputs 1 to 3.
- Recording of temperature values via remote sensors (see
accessories) at input 3.
- Up to 8 independent logic functions for implementing simple or
complex logical operations.
- Actively transmitting feedback or status messages can be
delayed after a bus voltage recovery or ETS programming mode.
- Bistable relay.
Switching functions
- NO contact or NC contact operation.
- Central switching function via up to 6 switch objects (ON, OFF,
permanently ON, permanently OFF).
- Feedback on switching: Active or passive feedback function.
- Reaction in case of bus voltage failure or bus voltage recovery
can be set following an ETS programming process.
- Logical linking function.
- Block function or forced setting function can be parameterised.
- Extended blocking function with acknowledgement option.
- Time functions (switch-on and switch-off delay, staircase light
function – also with advance warning function).
- Can be integrated in the light scenes: Up to 64 internal scenes
can be parameterised.
- Scene memory function: Additional visual feedback.
- Extended scene retrieval (toggling of scenes).
- Elapsed operating time meter can be activated.
- Input monitoring for cyclic updating of the switching object with
safety position.
Technical data
Rated voltage
- KNX:
DC 21 to 32 V SELV
Switching capacity:
AC 250 V, 16 AX
Maximum switch-on current:
800 A (200 µs), 165 A (20 ms)
Connected load
- Ohmic load:
2500 W
- Capacitive load:
16 A, max. 140 µF
- Motors (blind or fan):
1380 W
- Light bulbs:
2300 W
- HV halogen lamps:
2300 W
- HV LED lamps:
typically 400 W
- Wound transformer:
1200 VA
- Tronic transformer:
1500 W
- Fluorescent lamps,
uncompensated:
1000 VA
- Fluorescent lamps, duo-
circuit:
2300 VA
- Fluorescent lamps, parallel-
compensated:
1160 VA
Flush-mounted actuators
N New product.
Replaces 1059 00
KNX switching actuator, 1-gang 16 A with binary
input, 3-gang