367
Universal button interfaces KNX operating devices
Specifications
Order No.
P. unit
PS
Specifications
Order No.
P. unit
PS
Gira electrical installation systems
Price system (PS) ≠ 1, 14: reduced discount
KNX operating
devices
Flush-mounted binary inputs, can be used in deep device box
(60 mm deep) behind a conventional switch/push button, for
connection of zero-voltage contacts. The switching operations of
zero-voltage contacts are converted into KNX telegrams. The
inputs can be assigned various functions or blocked independently
of each other in the process. The inputs can be parameterised as
outputs (max. 2 mA).
Features
- Blocker for blocking individual inputs.
- Behaviour upon bus voltage recovery can be configured
separately for each input.
- Telegram rate limit.
- Two independent switching objects are available for each input
and can be released individually, command for leading and
trailing edge can be set independently (ON, OFF, CHANGE, no
reaction), cyclical transmission of the switching object depending
on the edge or depending on the object value can be selected.
- Single-surface and double-surface operation, time between
dimming and switching, and dim-step size can be set, telegram
repetition, and stop telegram transmission possible.
- Command can be set with rising edge (no function, UP, DOWN,
CHANGE), operating concept can be configured (Step - Move -
Step or Move - Step), time between short and long-term
operation can be set, slat adjustment time can be set.
Value transmitter and light scene auxiliary unit function:
- edge (button as NO contact, button as NC contact, switch) and
value with edge can be configured, value adjustment with button
by pressing and holding button for value transmitters possible,
light scene auxiliary unit with memory function and saving of the
scene without previously calling up is possible.
Temperature value transmitter and brightness value
transmitter function:
- edge and value configurable, value adjustment with push button
is possible by pressing and holding button.
Pulse counter function:
- edge for pulse counting and interval time for meter reading
transfer can be configured, edge of the synchronisation signal for
resetting the meter reading and switching telegram when
synchronisation signal arrives can be set.
Function of switching counter:
- edge for counting the signals at the input and maximum meter
reading selectable, increment for the counter reading output and
telegram when the maximum meter reading is reached can be
parameterised.
Function as switching output:
- Behaviour in case of bus failure and return, switch-on/off delay or
time switch function, output clocking (flashing of an LED).
Technical data
KNX medium:
TP256
Ambient temperature:
-5 °C to +45 °C
Dimensions in mm
W 43
H 28
D 15
1118001118 00
1/5
06
C Optional accessories
rocker btn 4-g NO con. 1-p 0147 00
D
166
junction box 0070 30
D
134
condensation sens. 5069 00
D
461
leakage sensor 5068 00
D
461
Features
- 2-gang flush-mounted binary input The two inputs can be
assigned various functions or blocked independently of each
other in the process. Both inputs can be configured as outputs
(max. 2 mA).
- Free assignment of the functions switching, dimming, blind and
value transmitter to both inputs or pulse counters and switching
counters.
Technical data
Number of inputs:
2
Connections
- KNX:
Connection and junction terminal
- Input line:
3-wire cable set
Scope of supply
- KNX connection and junction terminal included in the scope of
supply.
1119001119 00
1/5
06
C Optional accessories
rocker btn 4-g NO con. 1-p 0147 00
D
166
junction box 0070 30
D
134
condensation sens. 5069 00
D
461
leakage sensor 5068 00
D
461
Features
- 4-gang flush-mounted binary input. The four inputs can be
assigned various functions or blocked independently of each
other in the process. Two of the four inputs can be parameterised
as outputs (max. 2 mA).
- Free assignment of the functions switching, dimming, blind and
value transmitter to inputs 1 through 4 or pulse counters and
switch counters to inputs 1 and 2.
Technical data
Number of inputs:
4
Connections
- KNX:
Connection and junction terminal
- Input line:
5-wire cable set
Scope of supply
- KNX connection and junction terminal included in the scope of
supply.
Universal button interfaces
KNX universal button interface, 2-gang
KNX universal button interface, 4-gang