193
Dimming Gira System 3000
Specifications
Order No.
P. unit
PS
Specifications
Order No.
P. unit
PS
Gira electrical installation systems
Price system (PS) ≠ 1, 14: reduced discount
System 3000
Inserts, top units
5406005406 00
1
02
C Necessary accessories
One of the following articles:
System 3000 system top units
S3000 op.top 5360 ..
D
198
S3000 op.top arrows 5361 ..
D
198
S3000 touch top 5365 ..
D
198
S3000 op.top 2-g 5362 ..
D
199
S3000 op.top Memory arrows 5363 ..
D
199
S3000 blind timer + timer Display 5366 ..
D
199
S3000 op.top BT 5368 ..
D
200
S3000 blind timer + timer BT 5367 ..
D
200
System 3000 motion detector top units
S3000 mot.det.top 1.10 m Standard 5373 ..
D
202
S3000 mot.det.top 1.10 m Komfort BT 5374 ..
D
203
S3000 mot.det.top 2.20 m Standard 5375 ..
D
204
S3000 mot.det.top 2.20 m Komfort BT 5376 ..
D
204
S3000 pres. + mot.det. 360° top BT 5377 02
D
205
KNX RF operating top units
KNX RF op.top 1-g 5104 ..
D
380
KNX RF op.top 1-g arrows 5105 ..
D
380
KNX RF op.top 1-g heat.mode 5106 ..
D
380
KNX RF op.top 2-g 5107 ..
D
380
KNX RF op.top 2-g arrows 5108 ..
D
381
System 3000 wireless operating top units
Gira eNet WL op.top 5495 ..
D
484
Gira eNet WL op.top arrows 5494 ..
D
484
Gira eNet WL op.top Memory 5493 ..
D
485
Gira eNet WL op.top Memory arrows 5492 ..
D
485
C Optional accessories
Auxiliary inputs
S3000 aux.ins. 2-wire 5408 00
D
194
S3000 aux.ins. 3-wire 5409 00
D
194
S3000 rot.aux.ins. 3-wire 2389 00
D
195
rocker btn NO con. 0151 00
D
165
Features
- For switching on/off and adjusting brightness for lights with a
DALI interface
- Adjustment of colour temperature for lights with DALI Device
Type 8 for Tunable White according to IEC 62386-209.
- Connecting auxiliary units is possible.
- DALI power supply for 18 DALI devices.
- Parallel connection of up to 4 DALI Power control units to supply
up to 72 DALI devices.
- Save the minimum brightness, the coolest and warmest colour
temperature.
- Switch on with the last brightness/colour temperature set, or a
saved brightness/colour temperature.
- With System 3000 operating top unit, 2-gang: Setting the colour
temperature using the right-hand rocker.
Combination with KNX RF operating top unit, 1-gang/2-gang
- Dimming actuator, 1-gang.
- Sensor channel, 1-gang or 2-gang.
- Brightness and colour temperature control can be adjusted
separately.
- Local control of System 3000 insert possible.
- Wireless control of other KNX devices as sensor possible.
- Temperature detection.
- Insert function selection:
Staircase function, scene function, blocking function, time
delays.
Auxiliary input can be used as an additional operating point for
the System 3000 insert or for wireless control of other KNX
devices as a sensor.
Technical data
Rated voltage:
AC 230 V, 50/60 Hz
Power consumption:
max. 2.8 W
DALI rated voltage:
DC 16 V (typ.)
Output current:
max. 36 mA
Number of DALI devices:
max. 18
Number of DALI Power control
units that can be connected in
parallel:
max. 4
Colour temperature adjustment:
2000 to 10000 K
Auxiliary inputs
- Non-illuminated mechanical
buttons:
unlimited
- Auxiliary insert, 2-wire:
unlimited
- Auxiliary insert, 3-wire:
max. 10
Installation depth:
30 mm
Installation:
in device box pursuant to DIN
49073
Ambient temperature:
-5 °C to +45 °C
Gira System 3000 DALI power control unit,
flush-mounted insert