40
TaBEllE DI sElETTIvITà
Interruttore a monte
MB06 MB08 MB10 MB12 MB16
MA06 MA08 MA10 MA12
MA16
MA20 MA25
Interruttore a valle
In (A)
630
800
1000
1250
1600
630
800
1000
1250
1600
2000
2500
MB
630
T
T
T
T
T
T
T
T
T
T
T
T
800
T
T
T
T
T
T
T
T
T
T
1000
T
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
1600
T
T
T
T
MA
630
T
T
T
T
T
T
T
800
T
T
T
T
T
T
1000
T
T
T
T
T
1250
T
T
T
T
1600
T
T
T
2000
T
T
2500
T
Interruttore a monte
MH06 MH08 MH10 MH12 MH16
MH20 MH25 ML06 ML08
ML10
ML12
ML16
ML20
ML25 ML32 ML40
Interruttore a valle
In (A)
630
800
1000
1250
1600
2000
2500
630
800
1000
1250
1600
2000
2500
3200
4000
MB
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
1600
T
T
T
T
T
T
T
T
T
T
T
T
MA
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1000
T
T
T
T
T
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
T
T
T
T
1600
T
T
T
T
T
T
T
T
2000
T
T
T
T
T
T
2500
T
T
T
T
MH
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1000
T
T
T
T
T
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
T
T
T
T
1600
T
T
T
T
T
T
T
T
2000
T
T
T
T
T
T
2500
T
T
T
T
ML
630
T
T
T
T
T
T
T
T
T
800
T
T
T
T
T
T
T
T
1000
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
1600
T
T
T
T
T
2000
T
T
T
T
2500
T
T
T
3200
T
T
4000
T
T= selettività totale (il valore di selettività è il minore tra i poteri di interruzione (Icu) dell’interruttore a valle e dell’interruttore a monte)
Nota: I valori di selettività indicati in tabella si riferiscono ad interruttori opportunamente coordinati e regolati su soglie e tempi di intervento per sovraccarico e cortocircuito.
meGabreak a monTe eD a Valle in sisTema Trifase a 400Va.c.