IK DEGREE
GRADO IK
CLASS PROTECTION
CLASES DE PROTECCIÓN
IK DEGREE
GRADO IK
PROTECTION AGAINST EXTERNAL MECHANICAL IMPACTS
PROTECCIÓN CONTRA IMPACTOS MECÁNICOS EXTERNOS
DESCRIPTION
DESCRIPCIÓN
IK00
No protection / Sin proteger
IK01
Protected against 0.150J impact.
Protegido contra impacto de energía 0.150J.
Resistant against an impact of an object of 200 grs launched from a distance of 7.5 cm.
Resistente contra un impacto de un objeto de 200 grs lanzado desde una distancia de 7,5 cm.
IK02
Protected against 0.200J impact.
Protegido contra impacto de energía 0.200J.
Resistant against an impact of an object of 200 grs launched from a distance of 10 cm.
Resistente contra un impacto de un objeto de 200 grs lanzado desde una distancia de 10 cm.
IK03
Protected against 0.350J impact.
Protegido contra impacto de energía 0.350J.
Resistant against an impact of an object of 200 grs launched from a distance of 17.5 cm.
Resistente contra un impacto de un objeto de 200 grs lanzado desde una distancia de 17,5 cm.
IK04
Protected against 0.500J impact.
Protegido contra impacto de energía 0.500J.
Resistant against an impact of an object of 200 grs launched from a distance of 25 cm.
Resistente contra un impacto de un objeto de 200 grs lanzado desde una distancia de 25 cm.
IK05
Protected against 0.700J impact.
Protegido contra impacto de energía 0.700J.
Resistant against an impact of an object of 200 grs launched from a distance of 35 cm.
Resistente contra un impacto de un objeto de 200 grs lanzado desde una distancia de 35 cm.
IK06
Protected against 1.00J impact.
Protegido contra impacto de energía 1.00J.
Resistant against an impact of an object of 500 grs launched from a distance of 20 cm.
Resistente contra un impacto de un objeto de 500 grs lanzado desde una distancia de 20 cm.
IK07
Protected against 2.00J impact.
Protegido contra impacto de energía 2.00J.
Resistant against an impact of an object of 500 grs launched from a distance of 40 cm.
Resistente contra un impacto de un objeto de 500 grs lanzado desde una distancia de 40 cm.
IK08
Protected against 5.00J impact.
Protegido contra impacto de energía 5.00J.
Resistant against an impact of an object of 1,7 kg launched from a distance of 29,5 cm.
Resistente contra un impacto de un objeto de 1,7 kg lanzado desde una distancia de 29,5 cm.
IK09
Protected against 10.00J impact.
Protegido contra impacto de energía 10.00J.
Resistant against an impact of an object of 5 kg launched from a distance of 20 cm.
Resistente contra un impacto de un objeto de 5 kg lanzado desde una distancia de 20 cm.
IK10
Protected against 20.00J impact.
Protegido contra impacto de energía 20.00J.
Resistant against an impact of an object of 5 kg launched from a distance of 40 cm.
Resistente contra un impacto de un objeto de 5 kg lanzado desde una distancia de 40 cm.
El grado de protección IK es una clasificación numérica internacional para los grados de protección proporcionados por las envolventes de materiales eléctricos contra los impactos mecánicos
externos. Esto proporciona un medio para especificar la capacidad de un recinto para proteger su contenido de los golpes.
The degree of protection IK is an international numerical classification for the degrees of protection provided by enclosures of electrical equipment against external mechanical impacts.
This provides a means of specifying the ability of an enclosure to protect its contents from shock.
872
873
Class I:
Light fittings in which protection against electric shocks
does not depend solely on the mains insulation, but instead
contain an extra safety measure in the form of a circuit from
the accessible conductive parts with an grounded protective
conductor forming part of the installation’s fixed wiring, so that
the accessible conductive parts do not become dangerous
should there be a defect in the mains insulation. Ground
conductor is coloured green&yellow in most countries, and
just green in the U.S.,
Canada and Japan.
Class II:
A Class II or double insulated electrical appliance is one which
has been designed in such a way that it does not require a
safety connection to electrical ground. The basic requirement
is that no single failure can result in dangerous voltage
becoming exposed so that it might cause an electric shock
and that this is achieved without relying on an earthed metal
casing. This is achieved having two layers of insulating material
surrounding live parts or by using reinforced insulation.
Class III:
A Class III appliance is designed to be supplied from a
separated/safety extra-low voltage (SELV) power source.
The voltage from a SELV supply is low enough that under
normal conditions a person can safely come into contact with
it without risk of electrical shock. The extra safety features
built into Class I and Class II appliances are therefore not
required. For medical devices compliance with Class III is not
considered sufficient protection.
Clase I:
Luminarias en la que la protección contra los choques
eléctricos no recae exclusivamente sobre el aislamiento
principal, sino que comprende una medida de seguridad
suplementaria bajo la forma de medios de conexión de
las partes conductoras accesibles con un conductor de
protección puesto a tierra, formando parte del cableado fijo
de la instalación, de tal manera que las partes conductoras
accesibles no puedan llegar a ser peligrosas, en caso de
defecto del aislamiento principal. La toma tierra es de color
amarillo y verde en la mayoría de los países, y verde en los
Estados Unidos, Canadá y Japón.
Clase II:
Dispositivo de Clase II o aparato con doble aislamiento
eléctrico es uno que ha sido diseñado de tal forma que no
requiere una toma a tierra de seguridad eléctrica. El requisito
básico es que un fallo simple no puede dar lugar a tensiones
peligrosas que puedan causar una descarga eléctrica. Esto se
consigue mediante dos capas de material aislante rodeando
las partes con tensiones peligrosas o utilizando un aislamiento
reforzado.
Clase III:
Un aparato de Clase III está diseñado para ser alimentado
por una fuente de alimentación SELV (por sus siglas en
inglés: “Separated or Safety Extra-Low Voltage”). La tensión
de una fuente de SELV es lo suficientemente baja para que,
en condiciones normales, una persona puede entrar en
contacto con ella sin correr el riesgo de descarga eléctrica.
Por tanto, no es necesario incorporar la seguridad que llevan
los aparatos de Clase I y Clase II. Para el cumplimiento de los
dispositivos médicos la Clase III no se considera suficiente
para su protección.