189
INFORMATION
i
Electrical network
Regulatory
cable*
(in sheath)
* see national regulations.
Junction box
H07RN-F cable
(or equivalent)
Recessed box
Cable gland IP68
Recessed light 1
Recessed light 2
Layer of gravel
(minimum 30cm)
Resin
ILLUSTRATION OF A CONNECTION
THE DEPTH OF THE ELECTRICAL SHEATH
First of all, it is necessary to refer to national regulations.
Here is what we recommend:
- For an area not accessible to cars:
The electrical conduits must be buried at a minimum depth of 50 cm.
- For an area accessible to cars or under the sidewalks:
Electrical conduits must be buried to a minimum depth of 80 cm.
The buried electrical circuits must circulate in a sheath that can withstand shocks and crushing.
When covering these sheaths, it will be necessary to use soil or sand.
Under no circumstances should heavy stones be used to degrade the buried electric sheath with settlement.
THE CABLE
To ensure the tightness of the connection, with waterproof connectors or junction box, use a flexible rubber power cable type H07RN-F
or equivalent. A flexible, rubber cable is much easier to seal off against water. When the swivel of the ground spot is fastened to the
cable, the rubber cable sheath will function as a grommet. Nowadays, the cable will often be already attached to the ground spot. In
this case, you don’t need a separate cable.
Caution: if there’s a cable attached to the ground spot, don’t remove it! By doing this, you’ll lose your warranty.
INTEGRATION IN A WOOD FLOOR OR TERRACE
The drilling of the wood blades will be at the recommended drilling diameter (see product sheet, manual, etc ...). The depth under the
floor must allow to embed the spot and the waterproof connections. It is also necessary to ensure that there is sufficient space under
the recess to prevent stagnation of the water and not to «bend» the cable just at the exit of the cable gland. Otherwise, drainage will
be done.