I/O modules
DIN-RAIL MOUNT MODULES
EK-HU1-TP
Input/output module
for office applications
EK-HO1-TP
Input/output module
for hotel applications
30 Vdc power supply from bus
•
•
Auxiliary power supply 230 Vac 50/60 Hz
•
•
Analog Inputs
1
1
Freely programmable inputs as analogue or binary inputs
1
1
Binary inputs
3
9
Relay outputs 5 (3) A
2
4
Relay outputs 5 (3) A, for fan control
3
3
Relay outputs 16 (10) A, for heating and cooling valve control
-
2
Relay outputs for electric lock control
1
1
Relay outputs 16 (10) A
-
6
0-10 Vdc output
1
1
Membrane keypad for manual control of outputs
•
•
Function for ON/OFF lighting control
1
6
Function for roller shutters / awnings control
1
2
Function for electric strike control
-
•
Temperature control function
•
•
Switch-off scenarios and courtesy lights function
-
•
Logical functions
•
•
Description
The Ekinex® EK-FF1-TP binary output / blind actuator allows to command 16 groups
of loads or control 8 drives for motorised blinds independently. The device is fitted
with membrane pushbuttons for manual command (even in the absence of bus power)
and LED’s for status indication; a pushbutton allows to switch between automatic and
manual operation modes. The device integrates a KNX bus communication module
and is realized for mounting on a standard 35 mm DIN-rail. The device is supplied by
the KNX bus and requires an additional 230 Vac power supply to operate.
Main features
• Plastic casing
• Frontal programming pushbutton and LED
• Membrane keyboard with LED’s for status indication
• Pushbutton for switching operating mode (normal / programming)
• Connection to bus line with KNX terminal block
• Connection of outputs and 230 Vac power supply with screw terminals
• Overvoltage class III (according to EN 60664-1)
• Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
• Pollution degree 2 (according to IEC 60664-1)
• Installation on 35 mm rail (according to EN 60715)
• 8 modular units (1 MU = 18 mm)
• IP20 protection degree (installed device)
• Weight 595 g
Technical data
Power supply
• Voltage auxiliary 100-230 Vac 50/60 Hz
• Voltage control section 30 Vdc by KNX bus
• Current consumption from bus < 10 mA
• Power on bus < 240 mW
Outputs
• Number: 16 or 8 independent channels (depending on device use)
• Nominal voltage (Un): 100-230 Vac 50/60Hz
• Nominal current (In): max 16 (10) A (both @100Vac and @230Vac)
• Max. switched power: max 4000 VA @250Vac
Delivery
Delivery includes a terminal block for connection to the bus.
16-fold binary output/
8-fold blind actuator
ACTUATORS
Dimensions [mm]
144
5
25
20
20
70
90
45
3
4
1A
19
20
1B
21
22
2B
23
24
3B
25
26
4B
27
28
5B
29
30
6B
31
32
7B
33
34
8B
5
6
2A
7
8
3A
9
10
4A
11
12
5A
13
14
6A
15
16
7A
17
18
8A
1
2
L
N
bus KNX
1B
2B
3B
8B
1A
2A
3A
8A
EK-FF1-TP
16xD.O. 16(10)A/230Vac ~ 50/60 Hz
8xBlind 16(10)A/230Vac ~ 50/60 Hz
4B
5B
4A
5A
6B
7B
6A
7A
Dev.
Line
Area
Configuration and commissioning
By means of ETS5 software or later versions
Application program APEKFF1TP##.knxprod
(download from www.ekinex.com)
Documentation
For more information see the technical documentation,
download from www.ekinex.com
Order information
Code
Package
EK-FF1-TP
1 pcs.
TECHNICAL022EN
254
255
03
Introduction
18
Wall-mount devices
229
DIN-Rail mount modules
297
Supervision
311
Tools
315
Sales kit
321
Technical section
331
General terms of sale
335
General index