Power supply units
DIN-RAIL MOUNT MODULES
EK-AB1-TP
640 mA bus power
supply
EK-AG1-TP
640 mA bus power
supply with 30 Vdc
auxiliary output
EK-AM1-TP
1280 mA bus power
supply
Max. number of KNX devices that can be connected on KNX bus supply line
64
64
256
Reset of the connected bus line through pushbutton
•
•
•
LED for output voltage on KNX bus
•
•
•
LED for overload / short circuit on KNX bus
•
•
•
Integrated decoupling choke
•
•
•
Power supply 230 Vac
•
•
•
Power supply 176 ~ 280 Vdc
-
-
•
Output for auxiliary power supply 30 Vdc
-
•
•
Mounting on standard 35 mm rail (EN 60715)
•
•
•
System modules
DIN-RAIL MOUNT MODULES
Description
The Ekinex® 640 mA KNX bus power supply supplies and monitors the 30 Vdc voltage
required by the KNX bus for operation. An integrated choke provides for decoupling
power supply and bus line. On a bus line powered by a 640 mA power supply unit may
be connected a maximum of 64 bus devices. Output is protected from overload and
short-circuit. The EK-AG1-TP version is provided with an additional 30 Vdc output
can be used as auxiliary power supply for other devices requiring SELV voltage
(Safety Extra Low Voltage). The total current provided by the two outputs (KNX bus
line and auxiliary power supply) cannot exceed 640 mA. The device supports short
network voltage interruptions (max. 200 ms).
Main features
• Plastic casing
• Connection to bus line with KNX terminal block
• Connection of auxiliary output with dedicated terminal block (only EK-AG1-TP)
• Connection of 230 Vac power supply with screw terminals
• Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
• Pollution degree 2 (according to IEC 60664-1)
• Safety class II
• Installation on 35 mm rail (according to EN 60715)
• 4 modular units (1 MU = 18 mm)
• IP20 protection grade (installed device)
• Weight 150 g (EK-AB1-TP), 165 g (EK-AG1-TP)
Technical data
• Input voltage: 230 Vac, 50/60 Hz
• Power absorption 22 W
• Loss < 3 W
• Output voltage (KNX bus): 30 Vdc
• Output voltage (auxiliary output): 30 Vdc (only EK-AG1-TP)
• Nominal current (output total): 640 mA
• Buffer time: 200 ms
Delivery
Delivery includes one terminal blocks for connection to the bus; the EK-AG1-TP
version is delivered with a second terminal block for connection to the auxiliary
output.
640 mA bus power supply
POWER SUPPLY UNITS
Order information
Code
Version
Package
EK-AB1-TP
1 pcs.
EK-AG1-TP
with 30 Vdc auxiliary output
1 pcs.
Configuration and commissioning
Not necessary
Documentation
For more information see the technical documentation,
download from www.ekinex.com
Dimensions [mm]
EK-AB1-TP
EK-AG1-TP
72
90
45
70
5
25
20
20
bus KNX
AUX 30 V
1
2
3
L
N
Terminal block for auxiliary output (white/yellow) only on EK-AG1-TP version
EK-TM1-TP
Time / astronomical
digital switch
EK-BD1-TP
USB interface
EK-BA1-TP
Line / area
coupler
EK-IE1-SEC-TP
IP secure
interface
EK-IF1-SEC-TP
IP secure
router
Suppress device configuration on the sub line
-
-
•
•
•
Enable or disable filtering of group messages and suppress device oriented messages
-
-
•
•
•
Trace the traffic on the sub line and reduced number of retransmissions
-
-
•
•
•
Function pushbutton
•
-
•
•
•
Status LED for KNX bus line
-
•
•
•
•
Status LED for Ethernet
-
-
-
•
•
Mounting on standard 35 mm rail (EN 60715)
•
•
•
•
•
Plug in program
•
-
•
•
•
Programming pushbutton
-
•
-
•
•
Connection of a PC or laptop to the KNX bus system
-
-
-
•
•
Secure features
-
-
-
•
•
Time programming (daily, weekly, monthly or yearly) or astronomical
•
-
-
-
-
Control of 9 channels on bus
•
-
-
-
-
Channel 1 can be replicated on the relay on board
•
-
-
-
-
LCD-display
•
-
-
-
-
Backup battery
•
-
-
-
-
Connection of an optional GPS module
•
-
-
-
-
TECHNICAL022EN
232
233
03
Introduction
18
Wall-mount devices
229
DIN-Rail mount modules
297
Supervision
311
Tools
315
Sales kit
321
Technical section
331
General terms of sale
335
General index