TECHNICAL025EN
352
353
03
Introduction
17
Wall-mount devices
293
DIN-Rail mount modules
363
Visualisation
379
Audio Multiroom
427
IP Door Phone
445
Lift TV
457
Tools
461
Sales kit
466
Technical section
477
General terms of sale
481
General index
Documentation
For more information see the technical documentation,
download from www.ekinex.com
Gateway KNX / DALI 1 canale
GATEWAY
Description
Ekinex® Gateways EK-BF1-TP-D1 is a device used to control electronic control gear (ECG)
with a DALI interface (according to EN 62386) via the KNX installation bus. The device
converts switching and dimming commands from the connected KNX system into DALI
telegrams and status information from the DALI bus into KNX telegrams.
Connections
• KNX port with standard connector
• Screw terminals for DALI bus
Technical data
• Device power supply: 110-240 Vac or DC
• KNX bus power supply
Supply
The scope of delivery includes a terminal for connection to the KNX bus line and a 1.2 x 2
cm heat shrink tubing for additional insulation of the bus cable.
Other information
DALI® (Digital Addressable Lighting Interface) is a worldwide standard for interfacing
lighting control solutions whose data transmission protocol is contained in IEC
62386. DALI is a registered trademark of ZVEI (Zentralverband Elektrotechnik- und
Elektronikindustrie e.V.).
With firmware version 0.2.5 or higher, the device is certified according to EN 62386-
101 and -103 ed2 (DALI2) and therefore authorised to carry the DALI-2 logo.
Main features
Besides the pure gateway function, the EK-BF1-TP-D1 also offers numerous additional
functions:
• Addressing of up to 16 DALI groups or 63 individual ECGs
• Flexible DALI commissioning concept with ETS5
• Light colour control using type 8 ECG devices
• Light colour control according to different ECG subtypes
• Hourly programming for group and ECG control by value and/or colour
• Different operating modes such as permanent mode, night mode or staircase mode
• Integrated operating hours counter for each group and ECG with alarm when
maximum duration is reached
• Individual fault recognition with objects for each lamp / ECG
• Complex failure analysis at group/device level with calculation of the number of
failures and failure rate
• Fault threshold monitoring with individually configurable threshold values
• Scene module for extensive scene programming and dimming possibilities
• Quick replacement’ function for easy replacement of individual defective ECGs
• Manual control of group and broadcast telegrams via control buttons on the device
• Fault status signalling via LED on the device
Configuration and commissioning
ETS application v.5 and 6 for configuring the KNX functions of the device.
DCA App as special interface for configuring DALI segments.
Dimensions [mm]
Documentation
For more information see the technical documentation,
download from www.ekinex.com
Gateway KNX / DALI 2 canali
GATEWAY
Description
Ekinex® Gateways EK-BF1-TP-D2 is a device used to control electronic control gear (ECG)
with a DALI interface (according to EN 62386) via the KNX installation bus. The device
converts switching and dimming commands from the connected KNX system into DALI
telegrams and status information from the DALI bus into KNX telegrams.
Connections
• KNX port with standard connector
• Screw terminals for DALI bus
Technical data
• Device power supply: 110-240 Vac or DC
• KNX bus power supply
Supply
The scope of delivery includes a terminal for connection to the KNX bus line and a 1.2 x 2
cm heat shrink tubing for additional insulation of the bus cable.
Other information
DALI® (Digital Addressable Lighting Interface) is a worldwide standard for interfacing
lighting control solutions whose data transmission protocol is contained in IEC
62386. DALI is a registered trademark of ZVEI (Zentralverband Elektrotechnik- und
Elektronikindustrie e.V.).
With firmware version 0.2.5 or higher, the device is certified according to EN 62386-
101 and -103 ed2 (DALI2) and therefore authorised to carry the DALI-2 logo.
Main features
Besides the pure gateway function, the EK-BF1-TP-D2 also offers numerous additional
functions:
• Addressing of up to 2x16 DALI groups or 2x63 individual electronic ballasts
• Flexible DALI commissioning concept with ETS5
• Light colour control using type 8 ECG devices
• Light colour control according to different ECG subtypes
• Hourly programming for group and ECG control by value and/or colour
• Different operating modes such as permanent mode, night mode or staircase mode
• Integrated operating hours counter for each group and ECG with alarm when
maximum duration is reached
• Individual fault recognition with objects for each lamp / ECG
• Complex failure analysis at group/device level with calculation of the number of
failures and failure rate
• Fault threshold monitoring with individually configurable threshold values
• Scene module for extensive scene programming and dimming possibilities
• Quick replacement’ function for easy replacement of individual defective ECGs
• Manual control of group and broadcast telegrams via control buttons on the device
• Fault status signalling via LED on the device
Configuration and commissioning
ETS application v.5 and 6 for configuring the KNX functions of the device.
DCA App as special interface for configuring DALI segments.
Order information
Code
Application
Package
EK-BF1-TP-DP2
devices used to control electronic control gear (ECG) with
a DALI interface (according to EN 62386) via the KNX
installation bus
1 pcs.
Dimensions [mm]