37
SPECS
Rated power VA/W
3000/2100
INPUT
Nominal voltage
230V ± 25% single phase
Frequency
50/60Hz ± 5% auto sensing
Input Power Factor
> 0.98
OUTPUT
Voltage
220/230/240V ± 2% single phase, adjustable
Frequency
50Hz or 60Hz ± 0.5%
Waveform
Sinusoidal
Distortion (THD)
< 3%
Transfer time
0 ms.
DC start
Yes
Crest factor
03.01
Overload
120% for 1 minute, 150% per 10 seconds
BATTERY
Type
Sealed Lead Acid maintenance free
Recharge time
8h at 90%
Nominal voltage
96Vdc
Standard back up time
10 minutes
Supplementary charger
Optional 200W/500W chargers for extended backup application
PROTECTION
Short circuit
Hold whole System
Overheat
Switch to bypass
Noise suppression
Complies EN50091-2
Spike suppression
Complies EN61000-4-5
MISCELLANEOUS
Relative humidity
< 95% without condensing
Operating temperature
from 0°C to + 40°C
Noise
< 45 dBA
Interfaces
RS232 (dry contact, RS485, USB, SNMP and EPO optionally)
Compatible platforms
Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux
Inlet
1 x IEC 10A
Outlets Terminals
2x Shucko
Dimensions (mm)
190x453x365
Weight (kg)
36
STANDARDS
Safety
EN 62040-1-1
EMC
EN 62040-2, EN 61000-3-2, EN 61000-3-3, FCC A class
Marks
CE, UL, cUL
36
UPS - UNINTERRUPTIBLE POWER SUPPLY
On line double conversion UPS, meets today’s industry standard for energy saving and low reflected harmonic pollution to the
Utility. It uses a field proven MPU to substantially reduce the component count. This provides greater reliability, functionally and
smaller size than other designs. Using the latest high frequency techniques and quality components reliability is further increased.
High system efficiency is achieved in all operation modes saving electricity.
PRINCIPLES OF WORKING
The back up series is composed by: Rectifier, Inverter, Static Switch, manual by-pass and Battery.
The Rectifier-Inverter line normally feeds the users, and the Battery is kept charged by the Rectifier.
If a black out occurs, the Battery supplies power energy to users always through the Inverter. When the blackout is over, the
Rectifier provides for Battery charge. If a short circuit or an overload occurs to the users, the Static By-pass switches the load over
the emergency line. When the fault is over, the Inverter feeds users.
FEATURES
• Double conversion online technology;
• Filtered, stabilized and regulated sine wave supply;
• Unity Input power factor;
• Wide input voltage window and input frequency window, the battery usage is minimized;
• Zero transfer time;
• Add matching battery cabinets and extend the backup time up to several hours. With its isolation conversion technology plus
precision control, the optional charger can be installed in parallel up to 4 units;
• Superior overload capability;
• High battery reliability (battery test, manual and automatic);
• Optionally LCD display provides real time status and parameter readings;
• Smart battery management system monitors the battery charging and discharging status;
• Cold Start;
• Auto Restart;
• Plug & Play design;
• RS232 interface standard, dry contacts, USB, RS485 and SNMP as option.
CONTROL PANEL
LED display explanations:
By-pass, utility, inverter, battery low, overload, ups fault, load level % and battery level %.